WEKO3
アイテム
超高圧変電所の中性点接地線を用いた電磁気連続モニタリングの試み : 序報
https://doi.org/10.15083/0000032445
https://doi.org/10.15083/000003244502a14a4c-f45e-4280-8fde-2e39043c15c3
名前 / ファイル | ライセンス | アクション |
---|---|---|
IHO83302.pdf (2.5MB)
|
|
Item type | 紀要論文 / Departmental Bulletin Paper(1) | |||||
---|---|---|---|---|---|---|
公開日 | 2010-03-09 | |||||
タイトル | ||||||
タイトル | 超高圧変電所の中性点接地線を用いた電磁気連続モニタリングの試み : 序報 | |||||
言語 | ja | |||||
言語 | ||||||
言語 | jpn | |||||
キーワード | ||||||
主題 | neutral current of transformers | |||||
主題Scheme | Other | |||||
キーワード | ||||||
主題 | telluric field observation | |||||
主題Scheme | Other | |||||
キーワード | ||||||
主題 | geomagnetic variation | |||||
主題Scheme | Other | |||||
資源タイプ | ||||||
資源 | http://purl.org/coar/resource_type/c_6501 | |||||
タイプ | departmental bulletin paper | |||||
ID登録 | ||||||
ID登録 | 10.15083/0000032445 | |||||
ID登録タイプ | JaLC | |||||
その他のタイトル | ||||||
その他のタイトル | An Approach of the Continuous Electrical State Monitoring by Using the Ground Wire of Neutral Point at Extra-high Voltage Substations : A Preliminary Report | |||||
著者 |
井筒, 潤
× 井筒, 潤× 原田, 誠× 寺山, 武志× 植竹, 富一× 長尾, 年恭 |
|||||
著者別名 | ||||||
識別子 | 123746 | |||||
識別子Scheme | WEKO | |||||
姓名 | Izutsu, Jun | |||||
著者別名 | ||||||
識別子 | 123747 | |||||
識別子Scheme | WEKO | |||||
姓名 | Harada, Makoto | |||||
著者別名 | ||||||
識別子 | 123748 | |||||
識別子Scheme | WEKO | |||||
姓名 | Terayama, Takeshi | |||||
著者別名 | ||||||
識別子 | 123749 | |||||
識別子Scheme | WEKO | |||||
姓名 | Uetake, Tomiichi | |||||
著者別名 | ||||||
識別子 | 123750 | |||||
識別子Scheme | WEKO | |||||
姓名 | Nagao, Toshiyasu | |||||
著者所属 | ||||||
著者所属 | 中部大学地球ウオッチ・市民安全センター | |||||
著者所属 | ||||||
著者所属 | 東海大学地震予知研究センター | |||||
著者所属 | ||||||
著者所属 | 東京電力株式会社 | |||||
著者所属 | ||||||
著者所属 | 東京電力株式会社 | |||||
著者所属 | ||||||
著者所属 | 東海大学地震予知研究センター | |||||
抄録 | ||||||
内容記述タイプ | Abstract | |||||
内容記述 | We propose a new monitoring system by using the neutral current of transformers at substations of an electric power company named “neutral current monitoring”. It means that we have been measuring the telluric field by using the power line system in order to monitor the electromagnetic state of the underground over an extended time period. The principle of this system is as follow: the neutral points of the transformers in the substations are grounded to the earth and power lines connect them. If the neutral points of the transformers correspond to the grounded electrodes and the power line between substations corresponds to the electric wire between the electrodes, we can observe the telluric field and change of the electromagnetic structure of the underground between substations by measuring the current which flows at the neutral point of the transformer to some extent.We found that the neutral current is affected by various factors such as the geomagnetic changes and artificial noises like as the conventional telluric field observations. We would be able to investigate the underground electric conductivities near the substations by calculated response function between geomagnetic field data and neutral current data. | |||||
書誌情報 |
地震研究所彙報 巻 83, 号 3-4, p. 265-272, 発行日 2009 |
|||||
ISSN | ||||||
収録物識別子タイプ | ISSN | |||||
収録物識別子 | 00408972 | |||||
書誌レコードID | ||||||
収録物識別子タイプ | NCID | |||||
収録物識別子 | AN00162258 | |||||
フォーマット | ||||||
内容記述タイプ | Other | |||||
内容記述 | application/pdf | |||||
日本十進分類法 | ||||||
主題 | 51.1 | |||||
主題Scheme | NDC | |||||
出版者 | ||||||
出版者 | 地震研究所 | |||||
出版者別名 | ||||||
Earthquake Research Institute, University of Tokyo |